Our most important products > Current transformers > Current transformers (accuracy class 0,2S and 0,5S for billing measurement and special application)

Current transformers (accuracy class 0,2S and 0,5S for billing measurement and special application)

 
TypeMax. busbar (mm)Max. cable diameter (mm)Type test numberCurrent range (A)
AGS60/2020x1020Th-8779/6/202350-500
AGS60/3030x1024Th-8779/6/202350-750
AGS75/2020x1020Th-8779/6/202320-500
AGS75/3030x1024Th-8779/6/202350-800
AGS75/4040x1032Th-8779/6/202375-1000
AGS85/4040x1032Th-8779/6/202375-1000
AGS85/6060x1053Th-8779/6/2023120-1500
AGS105/6060x1053Th-8779/6/202375-1600
AGS105/8080x1064Th-8779/6/2023200-2000
AGS140/100100x3085Th-8779/6/2023100-3000
AMT-0-Vfitted-Th-5001/6/200850-1000

 

Technical dataAGS../..
AMT-0-V
 
Max. system voltage:0,72 kV0,72 kV
Test voltage:3 kV3 kV
Nominal frequency:50 Hz50 Hz
Rated primary current In:see on datasheetssee on datasheets
Nominal load capacity:see on datasheetssee on datasheets
Nominal secondary current:1A or 5A1A or 5A
Rated short time current Ith:40 x In (1 s)60 x In (1 s)
Nominal surge current Idyn:2,5 x Ith2,5 x Ih
Rated continous thermal current:1,2 x In1,2 x In
Instrument security factor:FS5, FS10FS5, FS10
Temperature class:BB
Ambient temperature:-25°C - 40°C-25°C - 40°C
Storage temperature:-40°C - 60°C-40°C - 60°C
Protection degree (secondary clip cover):IP20IP20
Standards:EN 61869-1; EN 61869-2EN 61869-1; EN 61869-2
Flammibility:UL94 V-0-
Compliant with RoHS directiven :YesYes
Fastening system (cable, busbar):Yes-
Fitted busbar, resin filled:-Yes
Data sheet:Safety datasheet which leave „VOID” text after removalAluminium, riveted